Free shipping for orders over £250! (Exc. VAT)

First Time Customer Discount

Get 5% of your first order! T&C

FIRSTFIVE

Part L Pipe Insulation Guide for Plumbers: Thickness, Materials & Compliance Checklist

Part L Pipe Insulation Guide for Plumbers: Thickness, Materials & Compliance Checklist

Jonathan Hill

Plumber's Compliance Guide

Part L pipe insulation can look straightforward until you have to decide which pipes need insulating, what thickness is required and whether a particular insulation material actually meets the specification.

This guide breaks the current England requirements down into practical terms for plumbers, heating engineers and mechanical contractors — including the key thickness tables, how thermal conductivity affects the answer, common installation mistakes and a final compliance checklist.

Installer fitting foil faced mineral wool pipe insulation around mechanical pipework
Check these before choosing insulation
Pipe Size OD / nominal bore
Thickness Required wall
Lambda W/(m·K)
Service Heating / DHW / chilled
Quick Answer

What thickness pipe insulation does Part L require?

There is no single Part L insulation thickness for every pipe. The correct thickness depends on whether the work is domestic or non-domestic, the pipe diameter, service temperature, insulation thermal conductivity and the relevant project specification.

Under the current Approved Document L guidance for dwellings in England, one route to demonstrating acceptable heat loss uses high-performance insulation with thermal conductivity of 0.025 W/(m·K) or better. The listed minimum thicknesses are 5mm, 10mm, 15mm or 20mm, depending on nominal internal pipe diameter.

Commercial and non-domestic systems use different tables and can require substantially greater insulation thicknesses.

August 2026

Current England position: the 2021 Approved Document L, incorporating the 2023 amendments, remains the current technical guidance for buildings subject to those standards. A 2026 edition has already been published but generally starts taking effect during 2027. Always check the regulatory basis and transitional arrangements for the individual project.

Before Using the Tables

Does Part L apply everywhere in the UK?

No. The Approved Document L figures discussed in this guide are for England.

Wales publishes its own Approved Document L, while Scotland and Northern Ireland operate under their own building standards and regulations. For work outside England, check the applicable national guidance before using the thickness tables below.

Plumber's rule: establish the project location and regulatory edition before ordering insulation. A thickness taken from the right table for the wrong country or project standard is still the wrong specification.
Domestic Pipework

Which pipes need insulating under Part L?

For a new system in a dwelling, current Approved Document L guidance for England identifies several categories of new pipework that should be insulated.

1

Heating circuits

Primary circulation pipes should be insulated where they pass outside the heated living space, including pipework passing into voids.

2

Domestic hot water

Primary domestic hot-water circulation pipework and all secondary circulation pipework are included.

3

Hot-water cylinders

Pipes connected to a hot-water storage vessel should be insulated for at least 1m from their connection to the vessel.

When a boiler or hot-water storage vessel is replaced in an existing system, Approved Document L also states that accessible pipes in the dwelling should be insulated.
Current England Guidance

Part L pipe insulation thickness for dwellings

Approved Document L Volume 1 states that heat losses from insulated pipework should not exceed the values given in BS 5422 for hot-water services at 60°C. Its Table 4.4 provides one way of demonstrating this using high-performance insulation with a thermal conductivity of 0.025 W/(m·K) or better.

Nominal internal pipe diameter Minimum insulation thickness Condition
≤ 10mm 5mm λ ≤ 0.025 W/(m·K)
≤ 25mm 10mm λ ≤ 0.025 W/(m·K)
≤ 50mm 15mm λ ≤ 0.025 W/(m·K)
≤ 100mm 20mm λ ≤ 0.025 W/(m·K)

Important: These are not universal pipe-lagging thicknesses. They apply to the conditions stated in Approved Document L and insulation with λ of 0.025 W/(m·K) or better. For other circumstances, the document directs users to BS 5422.

15mm, 22mm and 28mm copper warning: plumbers normally identify copper tube using its outside diameter, while the Part L table above is written using nominal internal pipe diameter. Do not simply match a 22mm pipe to the “≤25mm” row without checking how the specification and product sizing are being defined.
Commercial & Non-Domestic

Are Part L insulation thicknesses different for commercial pipework?

Yes. Approved Document L Volume 2 uses separate indicative tables for low-temperature hot-water heating and domestic hot-water services in non-domestic buildings.

It also states that insulation thickness should be calculated in accordance with BS EN ISO 12241, with manufacturers normally able to provide performance information for individual insulation products.

Low-temperature hot-water heating

Nominal internal pipe diameter λ = 0.025 W/(m·K) λ = 0.040 W/(m·K)
≤ 10mm 15mm 30mm
≤ 15mm 15mm 35mm
≤ 25mm 20mm 40mm
≤ 32mm 20mm 45mm
≤ 40mm 25mm 45mm
≤ 80mm 25mm 50mm
≤ 100mm 30mm 55mm

Indicative Table 4.4 figures for low-emissivity faced insulation and LTHW heating systems up to 95°C. Other circumstances should be checked against BS 5422.

Domestic hot-water services in non-domestic buildings

Nominal internal pipe diameter λ = 0.025 W/(m·K) λ = 0.040 W/(m·K)
≤ 10mm 15mm 35mm
≤ 20mm 20mm 35mm
≤ 40mm 25mm 40mm
≤ 80mm 25mm 45mm
≤ 100mm 30mm 45mm

These figures relate to hot-water services at 60°C and low-emissivity faced insulation. They are an indicative compliance route rather than a substitute for the project specification.

The Number That Changes the Answer

Why does thermal conductivity affect insulation thickness?

Thermal conductivity — normally shown as λ or lambda in W/(m·K) — describes how readily heat passes through the insulation.

In simple terms, a lower lambda value means better thermal resistance for a given thickness. That is why two products installed on exactly the same pipe may require different insulation thicknesses to achieve the same heat-loss target.

Do not buy by thickness alone. A 20mm insulation section with one lambda value cannot automatically be treated as equivalent to another 20mm product manufactured from a different material.

The manufacturer's declared thermal performance, the temperature at which that value applies, the pipe service and the applicable standard all need to be considered.

Material Selection

Which type of pipe insulation is best for Part L work?

There is no single “Part L insulation material”. Compliance comes from the complete specification — material performance, thickness, application and installation quality.

Space Restricted

Phenolic pipe insulation

High thermal performance makes phenolic insulation particularly useful where the required heat-loss performance needs to be achieved within a restricted insulation thickness.

Explore Phenolic Pipe Insulation →
Heating & Plantrooms

Mineral wool pipe insulation

A common option for heating, hot-water and mechanical-services pipework, particularly where temperature performance and fire characteristics are important considerations.

Explore Mineral Wool Pipe Insulation →
Cold & Chilled Services

Rubber pipe insulation

Closed-cell elastomeric insulation is widely used on chilled-water, refrigeration and cold services where condensation control and a correctly sealed vapour barrier are important.

Explore Rubber Pipe Insulation →
External Pipework

Insulation with protective cladding

External insulation needs suitable weather protection. Options can include factory-applied PIB systems or insulation finished with an appropriate separate cladding system.

View Pipe Insulation Options →
Cold Services

Does Part L also cover chilled and cooling pipework?

For non-domestic buildings, current Approved Document L guidance states that cooling pipework should be insulated along its whole length, subject to the detailed provisions in the document.

The insulation should control heat gain, but cold-service design also needs to consider condensation. That makes correct vapour sealing particularly important.

A thermal thickness calculation alone does not guarantee a successful chilled-water installation. Joints, fittings, supports and penetrations through the vapour-control layer need to remain properly sealed.
Technical Standard

What is the relationship between Part L and BS 5422?

Part L sets the regulatory requirement to limit heat gains and losses from building services. BS 5422 provides a method for specifying thermal insulation requirements for pipework, tanks, vessels, ducts and equipment across a wide range of operating temperatures.

There is an important detail for contractors to be aware of: the current BSI edition is BS 5422:2023, while the current Approved Document L tables were produced against earlier BS 5422 provisions.

On specification-led projects: check exactly which edition of BS 5422 is stated in the consultant's specification, drawings or project documentation. Do not mix values from different editions simply because one table produces a convenient thickness.

For a wider explanation of UK insulation standards, see our UK Pipe Insulation Standards and Regulations Guide .

Site Installation

Common pipe insulation mistakes that can undermine compliance

Correct thickness on the delivery note does not automatically mean the finished installation performs as intended.

Leaving fittings uninsulated Gaps at bends, tees, flanges and valves can create significant breaks in the insulation system.
Using the wrong lambda value Do not apply the thickness from a 0.025 W/(m·K) table to insulation with poorer thermal conductivity.
Confusing pipe OD and internal diameter Check how the regulatory table, pipe specification and insulation product define their sizes.
Compressing insulation Crushed or badly fitted sections can reduce the effective thickness and thermal performance.
Leaving external insulation exposed Foil-facing alone should not automatically be assumed to provide the required long-term external weather protection.
Poor vapour sealing on cold pipes Unsealed joints can allow moisture into a chilled-water insulation system and undermine condensation control.
Assuming insulation prevents freezing Insulation slows heat transfer; it does not create heat. Exposed high-risk services may require trace heating.
Ignoring the project specification Consultant specifications may require performance above the minimum regulatory guidance.
Job-Site Checklist

Part L pipe insulation compliance checklist for plumbers

Before ordering or signing off the pipe lagging, work through these checks.

  • Confirm whether the project is in England, Wales, Scotland or Northern Ireland.
  • Establish whether the building is a dwelling or non-domestic.
  • Confirm which regulatory edition and transitional arrangements apply.
  • Identify the service: heating, DHW, chilled water, refrigeration or other.
  • Confirm the actual pipe size and how it relates to the table being used.
  • Check the insulation manufacturer's declared thermal conductivity.
  • Check that the lambda value is appropriate to the relevant temperature.
  • Select the thickness from the applicable Part L, BS 5422 or project specification.
  • Allow for bends, tees, valves, flanges, supports and other fittings.
  • Maintain vapour sealing on chilled and condensation-risk services.
  • Specify suitable cladding or protection for external installations.
  • Check whether frost-risk pipework also requires trace heating.
  • Keep relevant product data and specification information where required.
  • Check the finished installation rather than the straight pipe runs alone.
Trade & Project Support

Not sure which insulation thickness or material to order?

Send us your pipe sizes, service type, required insulation thickness, quantities, and any cladding or trace heating requirements. Our team will recommend the most suitable products or provide a tailored quote for your project.

Coming Next

Is Part L changing in 2027?

Yes. A new 2026 edition of Approved Document L has already been published for England, but its main commencement dates are in 2027 and transitional arrangements apply.

This is particularly important for projects being designed or tendered now but constructed after the new requirements take effect.

We have covered the forthcoming changes separately in our Future Buildings Standard 2026 Pipe & Duct Insulation Guide .

Do not automatically use the future 2026-edition thickness tables on current work. Establish which regulatory standard applies to the individual building and project first.
Frequently Asked Questions

Part L pipe insulation FAQs

Is pipe insulation required under Part L?

Yes, Part L contains requirements intended to limit heat gains and losses from building-services pipework. Exactly which pipework needs insulating depends on the building, service and nature of the work.

What thickness pipe insulation do I need?

There is no universal thickness. You need the pipe size, service, applicable building type and the insulation's thermal conductivity before selecting the correct thickness from the relevant guidance or project specification.

Is 9mm or 13mm pipe insulation Part L compliant?

It may be suitable in a particular application, but thickness alone cannot establish compliance. The insulation's thermal conductivity, pipe size, service conditions and applicable performance requirement must also be checked.

Does BS 5422:2023 replace Part L?

No. Part L is part of the Building Regulations framework, while BS 5422 is a technical standard used for specifying thermal insulation performance. They perform different roles and may be used together.

Do bends and valves need insulating?

They should be considered as part of the complete insulation system. Leaving significant fittings and interruptions uninsulated can increase heat loss and undermine the intended performance of otherwise correctly insulated straight pipework.

Does Part L apply to chilled-water pipework?

Approved Document L for non-domestic buildings includes cooling pipework requirements. Cooling pipework should also be designed with condensation control and vapour sealing in mind.

Can foil-faced mineral wool be left outside?

External insulation normally requires suitable long-term weather protection. Do not assume a standard foil facing alone is an appropriate exposed external finish; specify a suitable weatherproof cladding or covering system.

Will Part L pipe insulation requirements change in 2027?

New Approved Document L editions have been published for England and take effect during 2027, subject to the type of work and transitional arrangements. Check the regulatory basis of projects spanning the changeover period.

Need Help?

Need help choosing or pricing pipe insulation?

Whether you're ordering a few pipe sections or pricing a larger mechanical-services project, speak to our team, explore trade account options, or browse the full Insulation & More range.

Technical References

Sources and further reading

For regulatory or specification-led work, always check the current source documents rather than relying solely on summary guidance.

Primary references used for this guide:

Technical disclaimer: This article is intended as practical general guidance and does not replace the Building Regulations, Approved Documents, British Standards, manufacturer technical data or an individual project's mechanical-services specification. Requirements may vary according to system temperature, pipe dimensions, insulation properties, project location, building type and applicable transitional arrangements. Always confirm the project requirements before specifying or installing insulation.